ATEX Rated Digital Refrigerant Recovery Machine

MR53INT
Is the Recovery Machine dual voltage?
The MR53INT is 230v only, however we do sell the MR53UK which is 110v only.
How do I clean my recovery machine?
1. Wipe with damp cloth to clean the exterior. Do not use solvents. 2. When the mesh screen filter becomes dirty and clogged, it means it’s keeping your MR53INT/MR53UK working well and protected from contaminants entering the machine and causing damage. You need to clean or replace this screen often.
What is the high pressure cut-out set to?
The High pressure cut out is set to 550 psi / 38 bar.
Do I need to use a filter drier?
We recommend to use a filter drier on the input port and change it often to protect the MR53INT/MR53UK from contaminated refrigerants.
Is the MR53INT/MR53UK A3 approved / ATEX Rated?
Yes, the Recovery Machine is ATEX Rated can be safely used with all A3 refrigerant systems and is ATEX Rated
Is the MR53INT/MR53UK A2L approved?
Yes, the MR53INT/MR53UK is A2L ready and can be used with refrigerants such as R32, R1234ZE and R1234YF.
What is the over pressure protection on the recovery machine?
The High-pressure cut off switch activates at 38 bar (550 psig).
At what negative pressure will the recovery machine cut off?
20"hg negative pressure or 50cmHg negative pressure is the final recovery value when the machine will stop automatically.